Download Tecumseh VSAG511ZXTXM Performance Data Sheet

Transcript
VSAG511ZXTXM
TPC___preliminary
October 14, 2011
Parts/Specifications
Unit BOM
Unit MODEL
32T2642-2
VSAG511ZXTXM
Refrigeration RANGE
Design Pressure Low
Design Pressure High
Volts - HZ - Ph
Voltage Range
Min. Circuit Ampacity
Max. Fuse Size
-40°F to 10°F
181
450
200-230V 3~ 60HZ
180 - 253
13.90
25
Compressor
Compressor
Compressor
Compressor
VSAG494ZXT
VS121RT-008-A4
80
10.00
MODEL
BOM
LRA
RLA
OverLoad
Relay
Run Capacitor
Run Capacitor Rating
Start Capacitor
Start Capacitor Rating
Contactor
INTERNAL
91014B
Unit Drawing
Wiring Diagram
DGU1950-12
WD23-2FL
Fan Motor
Fan Motor Qty
Fan Motor RLA
Fan Blade
Fan Guard
Shroud
810F050C20
2
0.7
51568-1
70831
70648-2
High Pressure switch
Low Pressure Control
Dual Pressure Conrol
84095-2
84026-2
Condenser
Head Master Valve
Check Valve
Process Valve
Liquid Valve
Suction Valve
50858
Receiver
Receiver Qty
Accumulator
Liquid Filter
Sight Glass
Suction Filter
51099-2L
1
TK00042000
52000-084D
70084-2
70822-5S
31529-2
CrankCase Heater
NOTES
IMPORTANT:
COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD
PROTECTOR. ALLOW TIME FOR RESET.
USE COPPER CONDUCTORS ONLY.
(EMPLOYER DES CONDUCTEUERS DE CUIVER
SEULEMENT.)
FIELD WIRING NOTES
1.
ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL
APPLICABLE LOCAL AND NATIONAL CODES.
2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY
TO L1, L2, AND L3 IN COMPRESSOR CONTACTOR OR TO L1, L2 AND L3 IN
DISCONNECT SW ITCH (IF PROVIDED). USE COOPER CONDUCTORS
ONLY. (EMPLOYER DES CONDUCTEURS DE CUIVER SEULEMENT.)
PROVIDE EQUIPMENT GROUNDING CONDUCTOR.
USE 75°C (MIN.) WIRING
3. IF REQUIRED INSTALL SYSTEM REMOTE CONTROL BETW EEN P1 AND P2
IN TERMINAL BLOCK AND REMOVE THE JUMPER
FAN 1
FAN 2
GENERAL NOTES:
SOLENOID
LIQUID INJECTION
A. CONTACTOR COIL CIRCUIT IS FACTORY CONNECTED TO 230 V SOURCE IN
PANEL AS SHOWN
B. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR.
ALLOW TIME FOR RESET.
COMPRESSOR CONTACTOR
NO AUXILIARY SW ITCH
FFC1 (FFC2)
COMPRESSOR
CONTACTOR COIL
see note A
HP
DT
FFC1
FFC2
LP
LOW PRESSURE CONTROL
TERMINAL
BOARD
P1
RECEIVER
HEATER
FAN CONTROL 1 (2)
LP
P3
P2
HP
THERMOSTAT
HIGH PRESSURE SWITCH
POWER SUPPLY
208-230 / 60 / 3
L3
T3
L2
T2
L1
T1
DT
DISCHARGE LINE THERMOSTAT
FACTORY COMPONENTS
GRD
CRANK CASE
HEATER
COMPRESSOR
CONTACTOR
L1
L2
L3
T1
T2
T3
OPTIONAL FACTORY COMPONENTS
OPTIONAL FIELD COMPONENTS
COMPRESSOR
TERMINAL
BLACK
R
RED
YELLOW
REL
REVISION
L:\~ Andreea temp\ZZ Low Temp Scroll Datasheets\WORD_datasheets\Indoor units\VSAG511ZXTXM_preliminary.doc
DEC 21, 2010
C
S
CONDENSING UNIT WIRING, 230V 60Hz 3 Ph,
Liquid Injection Solenoid,
Fan control,
WD23-2FL
14/10/2011