Download Tecumseh VSAG511ZXTXM Performance Data Sheet
Transcript
VSAG511ZXTXM TPC___preliminary October 14, 2011 Parts/Specifications Unit BOM Unit MODEL 32T2642-2 VSAG511ZXTXM Refrigeration RANGE Design Pressure Low Design Pressure High Volts - HZ - Ph Voltage Range Min. Circuit Ampacity Max. Fuse Size -40°F to 10°F 181 450 200-230V 3~ 60HZ 180 - 253 13.90 25 Compressor Compressor Compressor Compressor VSAG494ZXT VS121RT-008-A4 80 10.00 MODEL BOM LRA RLA OverLoad Relay Run Capacitor Run Capacitor Rating Start Capacitor Start Capacitor Rating Contactor INTERNAL 91014B Unit Drawing Wiring Diagram DGU1950-12 WD23-2FL Fan Motor Fan Motor Qty Fan Motor RLA Fan Blade Fan Guard Shroud 810F050C20 2 0.7 51568-1 70831 70648-2 High Pressure switch Low Pressure Control Dual Pressure Conrol 84095-2 84026-2 Condenser Head Master Valve Check Valve Process Valve Liquid Valve Suction Valve 50858 Receiver Receiver Qty Accumulator Liquid Filter Sight Glass Suction Filter 51099-2L 1 TK00042000 52000-084D 70084-2 70822-5S 31529-2 CrankCase Heater NOTES IMPORTANT: COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR. ALLOW TIME FOR RESET. USE COPPER CONDUCTORS ONLY. (EMPLOYER DES CONDUCTEUERS DE CUIVER SEULEMENT.) FIELD WIRING NOTES 1. ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL APPLICABLE LOCAL AND NATIONAL CODES. 2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY TO L1, L2, AND L3 IN COMPRESSOR CONTACTOR OR TO L1, L2 AND L3 IN DISCONNECT SW ITCH (IF PROVIDED). USE COOPER CONDUCTORS ONLY. (EMPLOYER DES CONDUCTEURS DE CUIVER SEULEMENT.) PROVIDE EQUIPMENT GROUNDING CONDUCTOR. USE 75°C (MIN.) WIRING 3. IF REQUIRED INSTALL SYSTEM REMOTE CONTROL BETW EEN P1 AND P2 IN TERMINAL BLOCK AND REMOVE THE JUMPER FAN 1 FAN 2 GENERAL NOTES: SOLENOID LIQUID INJECTION A. CONTACTOR COIL CIRCUIT IS FACTORY CONNECTED TO 230 V SOURCE IN PANEL AS SHOWN B. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR. ALLOW TIME FOR RESET. COMPRESSOR CONTACTOR NO AUXILIARY SW ITCH FFC1 (FFC2) COMPRESSOR CONTACTOR COIL see note A HP DT FFC1 FFC2 LP LOW PRESSURE CONTROL TERMINAL BOARD P1 RECEIVER HEATER FAN CONTROL 1 (2) LP P3 P2 HP THERMOSTAT HIGH PRESSURE SWITCH POWER SUPPLY 208-230 / 60 / 3 L3 T3 L2 T2 L1 T1 DT DISCHARGE LINE THERMOSTAT FACTORY COMPONENTS GRD CRANK CASE HEATER COMPRESSOR CONTACTOR L1 L2 L3 T1 T2 T3 OPTIONAL FACTORY COMPONENTS OPTIONAL FIELD COMPONENTS COMPRESSOR TERMINAL BLACK R RED YELLOW REL REVISION L:\~ Andreea temp\ZZ Low Temp Scroll Datasheets\WORD_datasheets\Indoor units\VSAG511ZXTXM_preliminary.doc DEC 21, 2010 C S CONDENSING UNIT WIRING, 230V 60Hz 3 Ph, Liquid Injection Solenoid, Fan control, WD23-2FL 14/10/2011