Download Tecumseh VSAG515ZXTHM Performance Data Sheet

Transcript
VSAG515ZXTHM
TPC___preliminary
October 14, 2011
TECUMSEH HERMETIC
CONDENSING UNIT
Model
BOM
Air Cooled
Application
Refrigerant
VSAG515ZXTHM
32L3642-2E
3 ¾ HP
Low Temp
R404A
47.75
46.97
31.58
29.00
26.00
4.50
LIQUID 1/2"
SUCTION 7/8"
Dim. Enclosure(inch)*
VSAG515ZXTHM
L
W
29.40 47.75
*) Enclosure Mounting Holes, 26.25 x 58.5
Line connections
H
Suction
Liquid
31.58
7/8 Sweat
1/2 Sweat
Pumpdown
Air flow
Oil Ch.
Gross weight
90% @ 90oF
33.44
SCFM
Oz.
Lbs.
4200
55
550
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
T, °F
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
PSIG
5.5
8.0
10.7
14.0
17.1
19.3
24.5
28.8
33.5
36.5
43.7
BTUH
7000
8100
9300
10700
12100
13600
15200
16700
18300
19900
21400
85°F
Watts Head
2880
212
2990
216
3090
220
3190
224
3290
228
3390
232
3500
236
3620
240
3740
245
3870
251
4020
256
Cond T
93
94
95
96
98
99
100
101
103
104
106
BTUH
6900
7800
8900
10100
11300
12700
14100
15500
16900
18400
19700
Ambient Temperatures
95°F
100°F
Watts Head Cond T BTUH Watts Head
3090
243
102
6800
3220
261
3190
248
103
7700
3320
265
3290
252
105
8700
3420
269
3390
256
106
9800
3520
273
3490
259
107
11000 3610
277
3600
263
108
12300 3720
281
3700
268
109
13600 3820
285
3820
272
110
15000 3930
289
3940
277
111
16300 4060
294
4070
282
113
17700 4190
299
4210
287
114
19000 4330
304
Cond T
107
108
109
110
111
112
113
115
116
117
118
BTUH
6300
7000
7900
8900
10000
11100
12300
13500
14800
16000
17200
110°F
Watts Head
3520
299
3620
304
3710
308
3810
312
3900
316
4000
319
4100
323
4210
327
4330
331
4460
336
4590
341
Cond T
117
118
119
120
121
122
123
124
125
126
127
Performance @ 60 Hz, Return gas 40oF, SubCooling 5oF
PRELIMINARY PERFORMANCE DATA
L:\~ Andreea temp\ZZ Low Temp Scroll Datasheets\WORD_datasheets\Outdoor units\VSAG515ZXTHM_preliminary.doc
14/10/2011
VSAG515ZXTHM
TPC___preliminary
October 14, 2011
Parts/Specifications
STANDARD
Unit BOM
Unit MODEL
32L3642-2E
VSAG515ZXTHM
Refrigeration RANGE
Design Pressure Low
Design Pressure High
Volts - HZ - Ph
Voltage Range
Min. Circuit Ampacity
Max. Fuse Size
-40°F to 10°F
181
450
200-230V 3~ 60HZ
180 - 253
16.49
25
Compressor
Compressor
Compressor
Compressor
VSAG513ZXT
VS123RT-008-A4
80
9.98
MODEL
BOM
LRA
RLA
OverLoad
Relay
Run Capacitor
Run Capacitor Rating
Start Capacitor
Start Capacitor Rating
Contactor
INTERNAL
Unit Drawing
Wiring no Fan controls
DGU1950-L303
WD23-2XT2L
91014B
OPTIONAL
Fan Motor
Fan Motor Qty
Fan Motor RLA
Fan Blade
Fan Guard
Shroud
810S186B40
2
1.9
51528-3
70832
70611-1
High Pressure switch
Low Pressure Control
Dual Pressure Conrol
84095-2L
84026-2
Condenser
Head Master Valve
Check Valve
Process Valve
Liquid Valve
Suction Valve
50785-4
70083
56626
Receiver
Receiver Qty
Accumulator
Liquid Filter
Sight Glass
Suction Filter
51084
1
TK00042000
52000-164D
70084-2
70822-5S
CrankCase Heater
14947869
Adjustable Fan Ctrl (A)
LAFC-001
Defrost Timer (Tn)
LTCG-T2
Receiver Heater (R)
LHR-223
Solenoid Valve (S)
KSVC-285
Disconnect (D)
KDSG-301
BOM INDEX DESCRIPTION
31529-2
32xYYYY- 2ERA(F)TnDS
E Enclosure
R Receiver Heater
A Adjustable fan control
F Fixed fan Control
T1 Defrost timer option
T2 Defrost timer & Defrost Heaters Contactor
D Disconnect
S Solenoid liquid Valve (supplied loose)
NOTES
IMPORTANT:
COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD
PROTECTOR. ALLOW TIME FOR RESET.
USE COPPER CONDUCTORS ONLY.
(EMPLOYER DES CONDUCTEUERS DE CUIVER
SEULEMENT.)
4
3
X
N
1
2
DEFROST CONTROL
RANCO
8145-xx
PRECISION 6145-xx
FAN 1
DEFROST
HEATERS
CONTACTOR COIL
FIELD WIRING NOTES
1.
ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL
APPLICABLE LOCAL AND NATIONAL CODES.
2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY
TO L1, L2, AND L3 IN COMPRESSOR CONTACTOR OR TO L1, L2 AND L3 IN
DISCONNECT SWITCH (IF PROVIDED). USE COOPER CONDUCTORS
ONLY. (EMPLOYER DES CONDUCTEURS DE CUIVER SEULEMENT.)
PROVIDE EQUIPMENT GROUNDING CONDUCTOR.
USE 75°C (MIN.) WIRING
3. DEFROST HEATERS LOADS SHOULD NOT BE HIGHER THEN THE
MAXIMUM HEATERS LOAD INDICATED ON THE UNIT LABEL.
DEFROST HEATERS TO BE CONTROLLED WITH A CONTACTOR AS SHOWN
ON THE DIAGRAM.
COMPRESSOR CONTACTOR
NC AUXILIARY SWITCH
FAN 2
GENERAL NOTES:
SOLENOID
LIQUID INJECTION
A. CONTACTOR COIL CIRCUIT IS FACTORY CONNECTED TO 230 V SOURCE IN
PANEL AS SHOWN
B. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR.
ALLOW TIME FOR RESET.
COMPRESSOR CONTACTOR
NO AUXILIARY SWITCH
FC
COMPRESSOR
CONTACTOR COIL
see note A
HP
LP
FAN CONTROL
DT
LP
LOW PRESSURE CONTROL
TERMINAL
BOARD
P1
RECEIVER
HEATER
L2
L1
L3
T1
T3
F1
F2
HP
THERMOSTAT
HIGH PRESSURE SWITCH
POWER SUPPLY
208-230 / 60 / 3
L3
T3
L2
T2
L1
T1
DT
DISCHARGE LINE THERMOSTAT
FACTORY COMPONENTS
GRD
CRANK CASE
HEATER
COMPRESSOR
CONTACTOR
L1
L2
L3
T1
T2
T3
DEFROST
HEATERS
CONTACTOR
L1
L2
L3
T1
T2
T3
OPTIONAL FACTORY COMPONENTS
OPTIONAL FIELD COMPONENTS
BLACK
C
S
R
RED
YELLOW
CONDENSING UNIT WIRING, 230V 60Hz 3 Ph,
Liquid Injection Solenoid,
Fan control,
T1 & T2 defrost options
REL
REVISION
L:\~ Andreea temp\ZZ Low Temp Scroll Datasheets\WORD_datasheets\Outdoor units\VSAG515ZXTHM_preliminary.doc
MAR. 11, 2011
COMPRESSOR
TERMINAL
WD23-2XT2L
14/10/2011