Download Microscan MS-4 Specifications
Transcript
Chapter 9 Discrete I/O Noread Definition: Activates a discrete output whenever the symbol data is not decoded before the end of the read cycle. Output Polarity Definition: Sets the polarity of the discrete output. When set to Active Low polarity, and an output condition from the scanner is met, the output-1 pin on the scanner’s 15 pin connector go low for the time specified in Pulse Width. (See Table A-2, “MS-3 Laser Host Connector, 15-pin,” on page A-4.) Serial Cmd: Default: <K720,output on,polarity,pulse width,number to output on> Active Low Options: 0 = Active High 1 = Active Low Definition: Sets the time in 1mS increments that the discrete output remains active. Serial Cmd: <K720,output on,polarity,pulse width,number to output on> Default: 50 (50 mS) Options: 0 to 65535 (0 to 65.535 seconds). Divide the number entered on the command line by 1000 for time in seconds. Number to Output On Definition: Sets the number of events (matches, mismatches, noreads, etc. as configured by Output On) that must occur before activating the associated output. Usage: Serial Cmd: For example, if Number to Output On is set to 3 and Output 1 is set to Noread, then Output 1 will not be activated until 3 noreads have occurred. <K720, output on,polarity,pulse width,number to output on> Default: Options: 1 0 to 255 MS-3 Laser Scanner User’s Manual 9-5 9–Discrete I/O Pulse Width