Technology functions ErrorID Error message Description / to correct or avoid error 8083 DB is not a technology DB The DB specified at input parameter Axis or the technology DB were not found. 8084 Invalid technology DB • A technology object does not exist in the PLC for the technology DB specified at input parameter Axis. Download the current technology to the PLC, or change the DB number at input parameter Axis. • The user has written invalid data to the technology DB specified at input parameter Axis. In "Technology Objects Management", delete and then recreate the technology DB. 808B Parameter value of invalid REAL format Invalid floating-point format of at least one input parameter value. Check the input parameter values or the instance DB data. Invalid values can not be indicated in floating-point format. They are shown on hexadecimal format (DW16# ...). 6-78 CPU 317T: Technology Functions A5E00251798-03