Download Section 16 CREATING A FIELDBUS STRATEGY BY USING
Transcript
Creating a Fieldbus Strategy by using DF51 OPC Client (HMI) OPC Update Rate DFI OLE Server (OPC Server) Update Time DFI302 Background Time, Supervision Time & MVC Field Device Figure 16. 35 – SYSTEM302 Architecture The next steps must be configured in order to get a better and optimized time for each system. Background time One of the first parameters to be set is Background time (or Background traffic). The Syscon calculates the macrocycle according to the number of links in the configuration and allows the user to add a Background time. A minimum value is automatically set by Syscon, and must be calculate to have an ideal background to each Fieldbus Network. The Background time is calculated based on the formula used for the Fieldbus macrocycle. The macrocycle is composed of Operational and Background traffics. The ideal macrocycle for non-Redundant Systems is: Ideal macrocycle non-Redundant = ((30*NDEV)+(30*NEL))*1.2 The ideal macrocycle for Redundant Systems is: Ideal macrocycle Reduntant = ((60*NDEV)+(30*NEL))*1.2 Where, NDEV is the Number of Field Devices in the Fieldbus Network NEL is the Number of External Links (between Field Devices) After you know the ideal macrocycle, go to Fieldbus Attributes on Syscon and adjust the Background Traffic to the new and acceptable value. IMPORTANT Once adjusted in every Fieldbus Channel, run a complete configuration download. 16.19