Transcript
28 4.6 SCADAPack E Operational Reference Manual RTU Configuration Revisions The SCADAPack E RTU provides a revision number tracking facility for RTU configurations. The following rules are applied when configurations are changed. The RTU maintains the configuration revision numbers in non-volatile RTU memory. For further information see the SCADAPack E RTU Configuration Technical Reference Manual. CONFIGURATION MAJOR REVISION NO.: CONFIGURATION MINOR REVISION NO.: System Analog Point 50050 System Analog Point 50051 The CONFIGURATION MAJOR REVISION NUMBER is updated under the following conditions: When the SCADAPack E RTU configuration is built, or re-built with a complete configuration (.RTU file), the Major Revision Number is incremented by 1 If the Major Revision Number is written via System Analog Point 50050 The CONFIGURATION MINOR REVISION NUMBER is updated under the following conditions: When the SCADAPack E RTU configuration is built, or re-built with a complete configuration (.RTU file), the Minor Revision Number is reset to 0 When the RTU configuration is updated with an incremental configuration (.INC file), the Minor Revision Number is incremented by 1 When a Record Exchange modification is made to the RTU database for Point record attributes *, or Trend records If the Minor Revision Number is written via System Analog Point 50051 Record exchange configurations individually made to the following point attribute fields result in the Minor Revision Number not incrementing. Point Alarm Inhibit attribute Point Trend Inhibit attribute Point is Bad attribute The SCADAPack E Configurator does not individually change attributes, so the Minor Revision Number is updated, regardless of which attributes are modified. For more information on Record Exchange see the SCADAPack E RTU Configuration Technical Reference manual.