44 Parameter Register Interface 4.3.2.8 CAN Update Rate – DC Link Status Message This parameter specifies the rate at which DC Link Status CAN messages will be automatically transmitted by the firmware. This value specifies the period between message transmissions in terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission of this message. All other values (1ms – 65,535ms) are valid. 4.3.2.9 CAN Update Rate – Grid Voltage Status Message This parameter specifies the rate at which Grid Voltage Status CAN messages will be automatically transmitted by the firmware. This value specifies the period between message transmissions in terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission of this message. All other values (1ms – 65,535ms) are valid. 4.3.2.10 CAN Update Rate – Inverter Current Status Message This parameter specifies the rate at which Inverter A and Inverter B Current Status CAN messages will be automatically transmitted by the firmware. This value specifies the period between message transmissions in terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission of this message. All other values (1ms – 65,535ms) are valid. 4.3.2.11 CAN Update Rate – Grid Status Message This parameter specifies the rate at which Grid Status CAN messages will be automatically transmitted by the firmware. This value specifies the period between message transmissions in terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission of this message. All other values (1ms – 65,535ms) are valid. 4.3.2.12 CAN Update Rate – System Status Message This parameter specifies the rate at which System Status CAN messages will be automatically transmitted by the firmware. This value specifies the period between message transmissions in terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission of this message. All other values (1ms – 65,535ms) are valid. 4.3.2.13 CAN Update Rate - Alarm Status Message This parameter specifies the rate at which Alarm Status CAN messages will be automatically transmitted by the firmware. This value specifies the period between message transmissions in terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission of this message. All other values (1ms – 65,535ms) are valid. 4.3.2.14 CAN Broadcast Message Receive Enable This parameter determines whether or not the AFE controller will accept broadcast messages from the host controller. See reference document FS-0046 (“OzCan Protocol Function Specification”) for more details on the use of broadcast messages. The legal values for this parameter are encoded as follows: 0 = Do Not Accept Broadcast Messages 1 = Accept Group-wide Broadcast Messages (Module ID = 0) AFE Controller User’s Manual