Download AFE Controller User`s Manual

Transcript
44
Parameter Register Interface
4.3.2.8 CAN Update Rate – DC Link Status Message
This parameter specifies the rate at which DC Link Status CAN messages will be automatically
transmitted by the firmware. This value specifies the period between message transmissions in
terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission
of this message. All other values (1ms – 65,535ms) are valid.
4.3.2.9 CAN Update Rate – Grid Voltage Status Message
This parameter specifies the rate at which Grid Voltage Status CAN messages will be
automatically transmitted by the firmware. This value specifies the period between message
transmissions in terms of milliseconds. Setting this parameter to zero disables
automatic/periodic transmission of this message. All other values (1ms – 65,535ms) are valid.
4.3.2.10 CAN Update Rate – Inverter Current Status Message
This parameter specifies the rate at which Inverter A and Inverter B Current Status CAN
messages will be automatically transmitted by the firmware. This value specifies the period
between message transmissions in terms of milliseconds. Setting this parameter to zero
disables automatic/periodic transmission of this message. All other values (1ms – 65,535ms)
are valid.
4.3.2.11 CAN Update Rate – Grid Status Message
This parameter specifies the rate at which Grid Status CAN messages will be automatically
transmitted by the firmware. This value specifies the period between message transmissions in
terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission
of this message. All other values (1ms – 65,535ms) are valid.
4.3.2.12 CAN Update Rate – System Status Message
This parameter specifies the rate at which System Status CAN messages will be automatically
transmitted by the firmware. This value specifies the period between message transmissions in
terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission
of this message. All other values (1ms – 65,535ms) are valid.
4.3.2.13 CAN Update Rate - Alarm Status Message
This parameter specifies the rate at which Alarm Status CAN messages will be automatically
transmitted by the firmware. This value specifies the period between message transmissions in
terms of milliseconds. Setting this parameter to zero disables automatic/periodic transmission
of this message. All other values (1ms – 65,535ms) are valid.
4.3.2.14 CAN Broadcast Message Receive Enable
This parameter determines whether or not the AFE controller will accept broadcast messages
from the host controller. See reference document FS-0046 (“OzCan Protocol Function
Specification”) for more details on the use of broadcast messages. The legal values for this
parameter are encoded as follows:


0 = Do Not Accept Broadcast Messages
1 = Accept Group-wide Broadcast Messages (Module ID = 0)
AFE Controller User’s Manual