Download 2705-UM001A-EN-P, RediSTATION Operator Interface User Manual
Transcript
2-4 Installation and Mounting Setting the Data Rate DIP switches 7 and 8 set the data rate at which the RediSTATION communicates on the DeviceNet network. The factory default is 125K. OFF = 0 ON = 1 10 9 8 7 6 5 4 3 2 1 DeviceNet Data Rate 00 = 125K BPS 01 = 250K BPS 10 = 500K BPS 11 = Unused The data rate determines the maximum length of the DeviceNet cable. Data Rate Cable Length (Maximum) 125K BPS 500 meters (1600 feet) 250K BPS 200 meters (600 feet) 500K BPS 100 meters (300 feet) To set the DeviceNet data rate: 1. Refer to the table above to select the correct data rate. 2. Slide switches 7 and 8 to the appropriate ON/OFF positions. Setting the Output Fault State DIP switch 9 sets the state of the outputs (pilot lights) when the device detects an error. The factory default setting is to turn the outputs off when an error is detected. The station ignores push button presses in the error state. When communication is regained, the station updates itself and resumes operation. OFF = 0 ON = 1 10 9 8 7 6 5 4 3 2 1 Output Fault State 0 = Outputs Turn Off on Fault 1 = Outputs Hold Last State on Fault Output Fault States Description Outputs Turn Off on Error When communication is lost, the station turns off outputs. Outputs Retain Last State When communication is lost, the outputs remain in their last state. To change the fault state, slide switch 9 to the correct ON/OFF setting. Publication 2705-UM001A-EN-P