Overview of Alarms
SINAMICS-Alarms
Remedy:
201421
Adapting the topologies:
- check the component soft-wired connections against the hardware configuration of the drive unit in
the commissioning software and correct differences.
- parameterize the topology comparison of all components (p9906).
- parameterize the topology comparison of one components (p9907, p9908).
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/actual value comparison).
<location>Topology: Comparison different components
Message
value:
Component number: %1, component class target: %2, component class actual: %3, fault cause: %4
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to
one component. The component class, the component type or the number of connections differ.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex: aa = component number of the component, bb = component class of the target tolopology, cc = component class of the actual topology, dd = fault cause
dd = 01 hex = 1 dec:
Different component class.
dd = 02 hex = 2 dec:
Different component type.
dd = 03 hex = 3 dec:
Different Order No.
dd = 04 hex = 4 dec:
Different number of connections.
Note:
Component class, component type and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Check the component soft-wired connections against the hardware configuration of the drive unit in
the commissioning software and correct differences.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/actual value comparison).
201425
<location>Topology: Comparison serial number of a component is
different
Message
value:
Component number: %1, Component class: %2, Differences: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to
one component. The serial number is different.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
cc = number of differences
bb = component class
aa = component number of the component
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.