Overview of Alarms
03/2009
NCK alarms
Program Continuation:
61602
Clear alarm with the RESET key. Restart part program
[Channel %1: ] Block %2: Tool width incorrectly defined
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Plunge cutter is larger than the programmed groove width. Alarm triggered by following cycle:
CYCLE93.
Remedy:
Check tool or change program.
Program Continuation:
Clear alarm with the RESET key. Restart part program
61603
[Channel %1: ] Block %2: Recess type incorrectly defined
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Radii/chamfers at the groove base do not match the groove width. Face groove on a contour element
running parallel to the longitudinal axis is not possible. Alarm triggered by following cycle: CYCLE93.
Remedy:
Check parameter VARI.
Program Continuation:
Clear alarm with the RESET key. Restart part program
61604
[Channel %1: ] Block %2: Active tool violates programmed contour
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Contour violation in the relief cut elements due to the tool clearance angle of the tool used. Alarm triggered by following cycle: CYCLE95.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Use a different tool or check the contour subroutine.
Program Continuation:
Clear alarm with the RESET key. Restart part program
61605
[Channel %1: ] Block %2: Contour incorrectly programmed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Illegal relief cut element detected. Alarm triggered by following cycles: CYCLE76, CYCLE77,
CYCLE95.
Remedy:
Check contour program.
Program Continuation:
Clear alarm with the RESET key. Restart part program
61606
[Channel %1: ] Block %2: Error during contour preparation
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
An error has been found on conditioning the contour. This alarm is always related to one of NCK
alarms 10930...10934, 15800 or 15810. Alarm triggered by following cycle: CYCLE95.
Remedy:
Check contour subroutine.
Program Continuation:
Clear alarm with the RESET key. Restart part program
61607
[Channel %1: ] Block %2: Starting point incorrectly programmed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
The starting point reached before the cycle call does not lie outside the rectangle described by the
contour subroutine. Alarm triggered by following cycle: CYCLE95.
Remedy:
Check starting point prior to cycle call.
Program Continuation:
Clear alarm with the RESET key. Restart part program