Sum P, Q, S = f(t)
14.00
12.00
10.00
P, Q, |S|
8.00
6.00
4.00
2.00
0.00
-2.00
00 01:00:00
00 01:10:00
00 01:20:00
P_total [MW]
00 01:30:00
00 01:40:00
Q_total [MVAr]
|S_total| [MVA]
00 01:50:00
00 02:00:00
Figure 131 The power demand of substation TSS_5 for the 2AC network.
Now we will compare the power demand for the AC network in Figure 115 with Figure 131 for
the 2AC network using Excel-File PowerSupply2AC.xlsx. We see the power demand for the
2AC network is much higher than for the AC network. This is the case because for the AC
network we have two substations and for the 2AC network only one substation and one auto
transformer station. Therefore TSS_5 has to supply the total power and losses in the 2AC
network.
Another comparison can be done for the energy consumption. Figure 132 shows the energy
consumption of the AC network provided from both substations and Figure 133 for the 2AC
network provided only from TSS_5.
E = f(t)
3.000
2.500
E [MWh]
2.000
1.500
1.000
0.500
0.000
00 01:00:00
00 01:10:00
00 01:20:00
00 01:30:00
00 01:40:00
00 01:50:00
00 02:00:00
Sim: 1; Network: A-C; Substation: TSS_5; Power Supply: T1; Ref erence U: Rails_BB; Compared U: OCS_BB
Sim: 1; Network: A-C; Substation: TSS_80; Power Supply: T1; Ref erence U: Rails_BB; Compared U: OCS_BB
Figure 132 Energy supply from both TSS of the AC network in default configuration.