excom®-system components Technical data Table 105: Technical data AIH41Ex Type code AIH41Ex (passive) Supply voltage via the module rack, central power supply unit or power supply module Power consumption ≤ 3W Inputs 4 analog sensors Supply voltage ≥ 15.0 V DC at 22 mA (on transmitter) Input current 0/4…20 mA per input HART®-impedance ≥ 240 Ω Overcontrol ≥ 21 mA Undercontrol ≤ 3.6 mA Short-circuit ≤ 5 V (only with "Live zero") Wire-breakage ≤ 2 mA (only with "Live zero") Resolution 14 bit Linearity error ≤ 0.1 % (from end value) Temperature drift ≤ 0.005 %/K Rise time / fall time ≤ 50 ms (10…90 %) Ex-approval PTB 00 ATEX 2059 X Marking É II 2 (1) G Ex ib [ia] IIC T4 / II (1) D [Ex ia IIIC] Ex max. value (field circuits) Ex ia IIC/IIB – Open-circuit voltage U0 ≤ 7.2 V – Short-circuit current I0 ≤ 16 mA – Max. power P0 ≤ 29 mW Characteristic curve linear Max. internal inductance LI ≤ 0.11 mH Max. internal capacity CI ≤ 1.1 nF IIC IIB Max. external inductance L0 0.50 mH 2.0 mH Max. external capacity C0 60 nF 250 nF General information 130 Galvanic isolation to bus and for supply Protection class IP20 Ambient temperature -20…+70 °C Relative humidity 95 % at 55 °C per EN 60069-2 Vibration test and shock test per IEC 60068-2-6 and IEC 60068-2-27 D301266 0113 - excom®