Addendum – parameters Table 213: (Forts.) Parameter for TI40Ex R 286 Byte No. Bit No. Parameter name 4 Parameters for all channels Parameter values 0 to 3 Sensor type 0000: Pt100 (IEC 751) 0001: Pt200 (IEC 751) 0010: Pt400 (IEC 751) 0011: Pt1000 (IEC 751) 0100: Pt100 (JIS) 0101: Pt1000 (JIS) 0110: Pt100 (SAM 0111: Pt1000 (SAM 1000: Ni100 1011: Cu100 1101: 0…30 Ω (mΩ) 1110: 0…300 Ω (10mΩ) 1111: 0…3 kΩ (100 mΩ) 4/5 Filter (PT1) 00:off 01:0.1 s 10:2.6 s 11:29.2 s 6/7 Connection 00:2-wire/ 0 Ω basis 01:2-wire/ 8 Ω basis 01:3-wire 11:4-wire D301266 0113 - excom®