Diagnoses per EN 61158 6.7.9 Manufacturer-specific error codes Principally, the meaning of the transmitted error codes for each slot or each module type can be different in a modular slave. With excom® there are different interpretations for the gateway and for the I/O-modules: Table 180: Error codes for gateway diagnosis Table 181: Error code for the I/O-modules Error code No. Meaning 16 ROM-error 17 RAM-error 18 EEPROM-error 19 Starting up after a cold start 20 Different configuration (with redundancy) 21 Different firmware (with redundancy) 22 Error function of the internal bus (CAN-error) 23 Error function of the internal bus (passive) (CAN-error) 24 Error in power supply unit or power supply module 1 25 Error in power supply unit or power supply module 2 26 Starting up after Watchdog-Reset 27 Redundancy switch has taken place 28 Redundant gateway is missing 29 Redundant gateway is not ready 30 Redundant gateway has an error 31 Redundant gateway has no PROFIBUS-DP communication Code No. Meaning 16 Cable error 17 reserved 18 Internal address conflict 19 Unknown module type (Nominal-configuration) 20 Unknown module type (Actual-configuration) 21 reserved 22 Parameter not plausible (inconsistent). 23 to 29 reserved 30 HART® status error 31 HART® communication error D301266 0113 - excom® 243