excom®-system components
AIH41EX 4H
Note
Please take the bit assignment "AIH41Ex 4H" page 279
In this configuration, the module also sends 4 HART®-variables to the cyclic data communication.
Table 99:
Parameter for
AIH41Ex 4H
126
Parameter name
Value
Meaning
Cable monitoring
on
off
Cable monitoring is activated or deactivated.
Substitue value strategy
min. value
max. value
last valid value
Depending on the parameterization, the min.
value, the max. value, or the last valid value is set.
The max. value is 21 mA. The min. value is
0 mA for 0…20 mA and 3.6 mA for 4…20 mA.
Filter (PT1)
off
0.1 s
2.6 s
29.2 s
Activation of a software filter to generate an
average value.
Channel 1: SV1…SV4
Channel 2: SV1…SV4
Channel 3: SV1…SV4
Channel 4: SV1…SV4
on/off
on/off
on/off
on/off
Activation/deactivation of the secondary variable
SV1…4 of Channel 1…4
Note: Avoid activation of more than 4 secondary
variables. The module only displays the first 4
activated secondary variables.
D301266 0113 - excom®