excom®-system components AIH41EX 4H Note Please take the bit assignment "AIH41Ex 4H" page 279 In this configuration, the module also sends 4 HART®-variables to the cyclic data communication. Table 99: Parameter for AIH41Ex 4H 126 Parameter name Value Meaning Cable monitoring on off Cable monitoring is activated or deactivated. Substitue value strategy min. value max. value last valid value Depending on the parameterization, the min. value, the max. value, or the last valid value is set. The max. value is 21 mA. The min. value is 0 mA for 0…20 mA and 3.6 mA for 4…20 mA. Filter (PT1) off 0.1 s 2.6 s 29.2 s Activation of a software filter to generate an average value. Channel 1: SV1…SV4 Channel 2: SV1…SV4 Channel 3: SV1…SV4 Channel 4: SV1…SV4 on/off on/off on/off on/off Activation/deactivation of the secondary variable SV1…4 of Channel 1…4 Note: Avoid activation of more than 4 secondary variables. The module only displays the first 4 activated secondary variables. D301266 0113 - excom®