excom®-system components Gateway diagnosis The gateway also provides manufacturer-specific error codes next to standard diagnoses. For example, these are power supply unit errors or power supply module errors, project planning mistakes, internal communication, redundancy switches, etc. Table 18: Special error codes of the gateway diagnosis 58 Error code No. Meaning 16 ROM-error 17 RAM-error 18 EEPROM-error 19 Starting up after a cold start 20 Different configuration (with redundancy) 21 Different firmware (with redundancy) 22 Error function of the internal bus (CAN-error) 23 Error function of the internal bus (passive) (CAN-error) 24 Error in power supply unit or power supply module 1 25 Error in power supply unit or power supply module 2 26 Starting up after Watchdog-Reset 27 Redundancy switch has taken place 28 Redundant gateway is missing 29 Redundant gateway is not ready 30 Redundant gateway has an error 31 Redundant gateway has no PROFIBUS-DP communication D301266 0113 - excom®