Download ODMS (Front Cover)
Transcript
WBPEEUI350003B0 Table E-2. Open Data Management Server Database Fields Database Field Name1 Change On-line Tag Types Supported Default Value User Defined Updated by INFI 90 OPEN (continued) Format or Restrictions Description Analog input, analog output, DAANG, RMSC, batch block, and station Yes12 Blank Yes Yes 6 alphanumeric characters The engineering units that correspond to a VALUE field. The EUDESC labels are defined in the engineering unit table and associated with an index number. The index number is specified in the INFI 90 OPEN system. sZERO Analog input, analog output, RMSC, and batch block. Yes12 Blank Yes Yes Decimal number The user defined low process limit value. This field should be set to the actual INFI 90 OPEN low process limit value. The value format field determines the format to use. sSPAN Analog input, analog output, batch block, and RMSC Yes12 ??????? Yes Yes Decimal number The range of values determined by the user. The sZERO field value plus the sSPAN field value equals the high process limit value. This field should be set to the actual INFI 90 OPEN low process limit value. The VALUE format field determines the format to use. sHIGH ALARM LIMIT Analog input, analog output, DAANG, RMSC, batch block, and station Yes12 ??????? Yes Yes Decimal number The user defined high alarm limit. This field should be set to the actual INFI 90 OPEN high process limit value. The VALUE FORMAT field determines the format to use. sLOW ALARM LIMIT Analog input, analog output, DAANG, RMSC, batch block, and station Yes12 ??????? Yes Yes Decimal number The user defined low alarm limit. This field should be set to the actual INFI 90 OPEN low process limit value. The VALUE FORMAT field determines the format to use. sSIGNAL CHANGE% Analog input, analog Yes12 output, and batch block ??????? Yes Yes Decimal number The INFI 90 OPEN exception report change limit. This field defines the amount of change in signal span (in percent) required to trigger an exception report. This field should be set to the actual INFI 90 OPEN signal change percent. sCOMP RECORD Analog input, analog output, DAANG, RMSC, batch block, and station Yes No data compression for applicable tags or Station. No data compression for station tags Yes No No data compression or boxcar/slope. For station tags only: station no data compression or station boxcar/slope. Identifies a processing record which defines the type of data compression processing. sCOMP SIGNIF CHG Analog input, analog output, DAANG, RMSC, batch block, and station Yes ??????? Yes No Defined by VALUE FORMAT Determines the maximum amount the current value (in engineering units) can change from the last recorded value without violating boxcar limits. sCOMP INTERVAL Analog input, analog output, DAANG, RMSC, batch block, and station Yes 00000:00:00.0 Yes No HHHHH:MM:SS:T The maximum time that can elapse before a new compressed value is recorded. Where HHHHH is hours, MM is minutes, SS is seconds and T is tenth of seconds. If this value is negative then a compressed value is always recorded. eLIMIT ALARM Analog input, analog output, DAANG, RMSC, batch block, and station No OK No Yes OK, high, or low Indicates if a tag is in high or low alarm, or no alarm. eDEVIATION ALARM Analog input, analog output, DAANG, batch block, and station No OK No Yes OK, high, or low Indicates if a tag is in high or low alarm, or no alarm. ODMS DATABASE OPEN DATA MANAGEMENT SERVER DATABASE FIELDS E-7 sEUDESC