6.11.2 Local device monitor/test Note6.2 This operation is useful for debugging a program, monitoring local devices ( Section 9.14.2) in the program monitored by GX Developer. Note1 (1) Monitoring a local device Table6.10 shows the monitor operation when the CPU module executes three programs "A", "B", and "C" and D0 to D99 are set as a local device. (Three programs are to be executed in the order of A B C (END processing) A B....) Table6.10 Data displayed when three programs are executed Setting When the device is not set as a local device When the device is set as a local device Monitor device D0 (Local device) D0 in the program "C" is monitored. D0 in the displayed program is monitored. Note1 Note6.2 Universal The Q00UJCPU does not support the use of local devices. 6 - 40 D100 (Global device) D100 after the program "C" is executed is monitored. D100 after the program "C" is executed is monitored.