Download CLS User's Guide
Transcript
PID Tuning and Control Control Modes The next sections explain the different modes you can use to control a loop. On/Off Control On/Off control is the simplest way to control a process; a controller using On/Off control turns an output on or off when the process variable reaches a certain limit above or below the desired setpoint. You can adjust this limit, since Watlow Anafaze controllers use an adjustable spread. For example, if your setpoint is 1000 ºF, and your limit (spread) is 20 ºF, the output switches On when the process variable goes below 980 ºF and Off when the process goes above 1000 ºF. (The next diagram shows a process under On/Off control.) Proportional Control A process using On/Off control frequently cycles around the setpoint. When process variable cycling is unacceptable or the process or setpoint are variable, use proportional control. Proportional control, or Gain, eliminates cycling by increasing or decreasing the output proportional to the process variable's distance from the setpoint. The limits of proportional control are defined by the Proportional Band (PB); outside this band of control, the output is either 100% or 0%. For example--using the same values from the example above and a PB of 20º---the output is: • 50% when the process variable is 990 ºF • 75% when the process variable is 985 ºF • 100% when the process variable is 980 ºF or below. 98 CLS User’s Guide