Appendix B: Enhanced Process Control Remote Setpoint Remote Setpoint can be used to allow external equipment, such as a PLC or other control system, to provide an analog output (4-20 mA, 0-5 Vdc, etc.) used to change the setpoint of a loop. The method of configuring the Remote Setpoint is the same as Ratio Control. In the previous example, loop 1 would be the remote analog value and loop 2 would be the PID control loop. Both the remote setpoint feature and the PV retransmit feature can be used with PLC systems as the link between multi-loop PID control systems and PLC systems. For example, a 0-5 Vdc signal representing 0-300 ºF will be used as a remote SP input to the CLS. The input signal will be received on Loop 1 with the control being performed on Loop 2. Note that proper scaling resisters must be installed on the input of Loop 1 to allow it to accept a 0-5Vdc input. From the loop 1 input channel, select the Linear Input Type. Set HiPV = 300, LoPV =0, HiRDG = 100.0%, and LoRDG = 0.0%. Next go to loop 2 and enter the programming menus. Go to the Ratio Option Menu and press the YES key to select the Ratio Menu. Display LOOP PROCESS User Input UNITS SETUP LOOP 02 RATIO CONTROL? ALARM SETPOINT LOOP PROCESS STATUS OUT% Assign loop 01 to be the master loop. UNITS 02 RATIO CONTROL MSTR LOOP? 01 ALARM SETPOINT STATUS LOOP UNITS PROCESS 158 STATUS Press Enter. OUT% 02 RATIO CONTROL MIN SP? 0 ALARM SETPOINT Press Yes to setup the Ratio parameters for loop 02. OUT% Enter the minimum Ratio loop SP. For this example, we will use 0 ºF. Press Enter.