Setup Heat or Cool Control PB This menu allows you to set the Proportional Band (also known as Gain). LOOP PROCESS UNITS 02 HEAT CONTROL PB? 50 ºF ALARM SETPOINT STATUS OUT% NOTE The CLS internally represents the proportional band (PB) as a gain value. When you edit the PB, you'll see the values change in predefined steps--small steps for narrow PB values and large steps for wide PB values. The controller calculates the default PB for each input type according to the following equation: (High Range - Low Range) Default PB = Gain Heat or Cool Control TI This menu lets you set the Integral term, or Reset. LOOP PROCESS UNITS 02 HEAT CONTROL TI ? 180 Sec/R ALARM SETPOINT STATUS OUT% Selectable range: 0 (off) - 6000 seconds. Heat or Cool Control TD This menu lets you set the derivative constant. LOOP PROCESS UNITS 03 HEAT CONTROL TD ? 0 sec ALARM SETPOINT STATUS OUT% Selectable range: 0-255 seconds. CLS User’s Guide 79