TECUMSEH HERMETIC
CONDENSING UNIT
Model
BOM
Air Cooled
Application
Refrigerant
AVA4540EXNHN
TPC___rev 1
January 6, 2012
AVA4540EXNHN
32L3127-2E
3 HP
High Temp
R 22
36.25
35.25
26.08
23.50
26.43
3.00
„ 0.50 4 PLACES
MOUNTING HOLES
AVA4540EXNHN
SUCTION „ 7/8
Dimensions (inch)
L
W
H
26.43
36.25
26.08
LIQUID „ 1/2
Line connections
Suction
Liquid
7/8 Sweat
1/2 Sweat
Pumpdown
o
90% @ 90 F
22.41
Air flow
SCFM
Oil Ch.
Oz.
Gross weight
Lbs.
1550
55
280
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
o
F
10
15
20
25
30
35
40
45
50
55
Psig
32.8
37.7
43.0
48.7
54.8
61.4
68.5
76.0
84.0
92.6
o
BTUH
21400
24200
27100
30000
33000
36100
39300
42600
46000
49400
80 F
Watts
2980
3160
3350
3560
3770
4000
4250
4500
4770
5050
o
Cond T
100
102
105
108
111
114
118
121
125
128
BTUH
19600
22200
24900
27600
30500
33400
36300
39400
42500
45700
90 F
Watts
3060
3260
3460
3680
3900
4140
4390
4650
4930
5210
Cond T
109
112
114
117
120
123
126
129
133
136
Ambient Temeratures
o
95 F
BTUH Watts Cond T
18400
3030
115
21000
3290
117
23600
3530
120
26300
3770
123
29000
4010
126
31800
4240
129
34700
4460
132
37600
4670
135
40600
4880
139
43600
5070
142
o
BTUH
17300
19800
22400
25000
27700
30400
33100
35900
38800
41700
100 F
Watts
3100
3310
3540
3780
4030
4290
4550
4830
5120
5410
o
Cond T
119
121
124
127
129
132
135
138
141
144
L:\~ Andreea temp\~ DATA SHEETS\Outdoor Datasheets\WORD_Datasheets\High Temp Applications\AVA4540EXNHN_rev1.doc
BTUH
15500
17900
20400
22800
25300
27800
30400
32900
35500
38100
110 F
Watts
3130
3370
3610
3870
4140
4420
4710
5020
5330
5660
Cond T
128
130
133
136
138
141
144
147
150
153
06/01/2012
AVA4540EXNHN
TPC___rev 1
January 6, 2012
Parts/Specifications
STANDARD
Unit BOM
Unit MODEL
32L3127-2E
AVA4540EXNHN
Refrigeration RANGE
Design Pressure Low
Design Pressure High
Volts - HZ - Ph
Voltage Range
Min. Circuit Ampacity
Max. Fuse Size
(20°F to 55°F)
150
450
208-230V ~ 60HZ
187 - 253
28.05
50
Compressor MODEL
Compressor BOM
Compressor LRA
Compressor RLA
AVA5542EXN
AV144ET-001-A2
108
21.15
OverLoad
Relay
Run Capacitor
Run Capacitor Rating
Start Capacitor
Start Capacitor Rating
Contactor
INTERNAL
820ARR3H46
85PR440F28
40 MFD, 440 V
85PS330D16
130-156 MFD, 330 V
91014
Unit Drawing
Wiring Diagram
DGU1920-L101
WD21-2XT2
OPTIONAL
Fan Motor
Fan Motor Qty
Fan Motor RLA
Fan Blade
Fan Guard
Shroud
810F050C20
2
0.7
51568
70831
70648-2
High Pressure switch
Low Pressure Control
Dual Pressure Conrol
84095-1L
84026-D
Condenser
Head Master Valve
Check Valve
Process Valve
Liquid Valve
Suction Valve
50858
70083-1
56626
Receiver
Receiver Qty
Accumulator
Liquid Filter
Sight Glass
Suction Filter
51099-2L
1
TK00042000
52000-084D
SG-08DF
70822-5S
CrankCase Heater
90699
Defrost Clock (Tn option) 84110
Defrost Heaters Contactor 91014
Rec. Heater (R option)
Solenoid Valve (loose)
LHR-222
KSVC-264
Disconnect (D option)
LDSG-613
Wiring with A option
WD21-2AT2
BOM INDEX DESCRIPTION
31529-1
32xYYYY- 2ERA(F)TnDS
E Enclosure
R Receiver Heater
A Adjustable fan control
F Fixed fan Control
T1 Defrost timer option
T2 Defrost timer & Defrost Heaters Contactor
D Disconnect
S Solenoid liquid Valve (supplied loose)
NOTES
IMPORTANT:
FIELD INSTALLED
SOLENOID & THERMOSTAT
COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD
PROTECTOR. ALLOW TIME FOR RESET.
USE COPPER CONDUCTORS ONLY.
(EMPLOYER DES CONDUCTEUERS DE CUIVER
SEULEMENT.)
ROOM
THERMOSTAT
Solenoid
Valve
4
3
X
DEFROST CONTROL
RANCO
8145-xx
PRECISION 6145-xx
N
1
2
FAN 1
DEFROST
HEATERS
CONTACTOR COIL
FIELD WIRING NOTES
1.
ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL
APPLICABLE LOCAL AND NATIONAL CODES.
2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY
TO L1, AND L3 IN COMPRESSOR CONTACTOR (L1 AND L2 IF TWO POLE
CONTACTOR) OR TO L1 AND L3 IN DISCONNECT SWITCH (IF PROVIDED).
USE COOPER CONDUCTORS ONLY. (EMPLOYER DES CONDUCTEURS
DE CUIVER SEULEMENT.) PROVIDE EQUIPMENT GROUNDING
CONDUCTOR. USE 75°C (MIN.) WIRING
3. PLACE JUMPER ACCROSS P1 AND L1 IN TERMINAL BOARD IF NO
OTHER CONTROLLING DEVICE IS INSTALLED.
4. DEFROST HEATERS LOADS SHOULD NOT BE HIGHER THEN THE
MAXIMUM HEATERS LOAD INDICATED ON THE UNIT LABEL.
FAN 2
GENERAL NOTES:
COMPRESSOR CONTACTOR
NC AUXILIARY SWITCH
COMPRESSOR
CONTACTOR COIL
see note A
HP
A. CONTACTOR COIL CIRCUIT IS FACTORY CONNECTED TO 230 V SOURCE IN
PANEL AS SHOWN
B. WITH ANY T.P.Co. APPROVED START RELAY USED, CONNECT LEADS TO
SAME NUMBERED TERMINALS REGARDLESS OF LOCATION
C. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR.
ALLOW TIME FOR RESET.
LP
RECEIVER
HEATER
TERMINAL
BOARD
P1
L1
L2
L3
T1
T3
F1
F2
LP
LOW PRESSURE CONTROL
HEATER
THERMOSTAT
POWER SUPPLY
230-60-1
L3
T3
L2
T2
L1
T1
HP
HIGH PRESSURE SWITCH
FACTORY COMPONENTS
POTENTIAL RELAY
see note B
GRD
OPTIONAL FACTORY COMPONENTS
COMPRESSOR
CONTACTOR
L1
L2
L3
L1
L2
L3
T1
T2
T3
T1
T2
T3
4
5
6
1
CONDENSING UNIT WIRING, 230V 60Hz 1 Ph,
NO fan controls,
T1 & T2 defrost options
BLACK
C
S
OPTIONAL FIELD COMPONENTS
2
DEFROST
HEATERS
CONTACTOR
COMPRESSOR
TERMINAL
R
START
CAPACITOR
WITH BLEEDER
RESISTOR
RED
YELLOW
BLACK
RED
YELLOW
RUN
CAPACITOR
B
REVISION
NOV 06, 2009
CRANK CASE
HEATER
WD21-2XT2
L:\~ Andreea temp\~ DATA SHEETS\Outdoor Datasheets\WORD_Datasheets\High Temp Applications\AVA4540EXNHN_rev1.doc
06/01/2012