Technology functions ErrorID Error message 8089 808C Invalid data length (ANY pointer) Pointer format is invalid or not supported Description / to correct or avoid error Specified data length is invalid. Possible causes are: • The length exceeds 64 bytes • The specified length plus the start address defines an address outside of the I/O image DP(DRIVE). The ANY pointer contains illegal specifications. Accepted areas: I, O, M, DB, DI Accepted data types: BYTE, CHAR, WORD, INT, DWORD, DINT, REAL 808D Data record length out of range CPU 317T: Technology Functions A5E00251798-03 An attempt was made to transfer a data record with a length of more than 240 bytes. Reduce the length definition in the ANY pointer. 6-235