Download PDF - QuickSilver Controls, Inc.
Transcript
Initialization Commands See Also: Kill Motor Recovery (KMR) Kill Motor Conditions (KMC) Description: The Kill Motor Conditions allows the user to select what conditions will allow a controlled shutdown of the SilverMax unit. The Condition Enable word selects which bits in the Internal Status Word (ISW) will be evaluated (See Internal Status Word (ISW) in User Manual for bit definitions). Conditions are enabled by setting a “1” in the desired bit position of the Condition Enable binary word. The Condition State word allows the user to specify the state of the selected conditions that will cause the servo to do a controlled shutdown. Note: Over-voltage is always enabled whenever the driver is enabled to protect the drivers from over voltage. An over-voltage condition will always disable the drivers regardless of the of Kill Enable Drivers state. See Shutdown and Recovery in User Manual for details. Default has only Over Temperature enabled. Command Info: Command Name Command Type/Num Parameters Param Type Parameter Range Kill Motor Conditions (KMC) Program Class D 167 (0xA7) 3 Words Condition Enable U16 0 to 65535 Condition State U16 0 to 65535 Example: QuickControl Example: Shut down servo if any of the following conditions are met: I/O#1 LOW (bit 4) Over Temp (bit 7) Moving Error (bit 8) NOTE: Over Temp TRUE = 0. 4 7 8 Enable = 2 + 2 + 2 == 400 4 7 8 State = 2 *0 + 2 *0 + 2 *1=256 @16 167 400 256 (CR) SilverMax Response: ACK only SilverMax Command Reference 47 Revision 4.01