Download User`s Manual
Transcript
CHAPTER 11 RESETTING THE COMMUNICATION MODULE IN RUN MODE [Figure 11.3.5] shows the flag monitoring screen of the communication module installed in the main base. [Figure 11.3.5] flag value of main base communication module In order to reset the FEnet I/F module installed in slot no.’0’, double click the variable name (_FENET_RESET_M[0]). As shown below, the forced input window will appear, and the value can be input. In order to reset the FEnet I/F module, the user sets the relevant flags as ‘1’. The reset procedure is completed and cleared to ‘0’ again. [Figure 11.3.6] Forced input of the flag 11.3.2 Reset of the communication module through programming This method allows the user to reset the communication module directly through programming. The reset method and main action by the flag monitor is the same but it is also available to control the module by using a temporary contact without starting the GMWIN program. The user can control the CPU to perform the RESET by using the emergency contact of the program. The RESET will be performed by force by using the external interrupt contact. 1) Forced reset of the communication module through programming This method allows the RESET of the communication module through variable registration of the program. By registering the flag variable in the program, it is able to perform the RESET automatically/manually if necessary. 11-6