Download Manual - Festo
Transcript
4. Commissioning Physical addressing PLEASE NOTE Use the logical addressing or the bus configuration via the CMD software, providing your INTERBUS module permits this. In this way you can avoid input and output addresses being shifted during later extensions. The first bus slave is addressed with the basis address (BA) of the INTERBUS module. The address of the next bus slave is obtained by adding the relevant number of bits of the process data channel of all the previous slaves to the basis address. The procedure must be carried out separately for inputs and outputs. Example of physical addressing: 1st. terminal 2nd. SPC200 3rd. SPC200 4th. terminal 5th. terminal ... Process data channel bits 32 64*) 48*) 32 16 Physical address BA BA+32 BA+32+64 BA+32+64+ 48 BA+32+64+ 48+32+.... *) The field bus module of the SPC200 occupies the appropriate number of bits depending on the operating mode of the SPC200 and on the I/O configuration set with WinPISA (inputs/outputs, see Chapters 4.2.2 and 4.1.3). SPC200-COM-IBS 0503a 4-23