Download User Guide PLC WorkShop for Modicon

Transcript
PLC WorkShop for Modicon
Chapter 11 – Instructions, Transfer and move instructions
Figure 33 – IBKR instruction function block
Top Node
The 4x register is the first holding register in a source
table. The registers in this table contain values that are
pointers to the non-contiguous registers you want to
collect in the operation.
Middle Node
The 4x register is the first in a block of contiguous
destination registers.
Bottom Node
The value entered indicates the length (the number of
registers in the source table).
IBKW
DESCRIPTION
The Indirect block write (IBKW) instruction lets you copy the data from a table
continuous registers into several non-contiguous registers dispersed throughout your
application.
- 490 -