Chapter 11 – Instructions, Software Loadable Modules Description
Figure 59 – EARS Function Block
Top Node
State table pointer and history table. Contains the first
of 64 consecutive 4x registers. The first two of these
registers contain values that specify the location and
size of the current state table. The remaining two are
available for the history table.
Middle Node
Implied registers and buffer table.
Bottom Node
Contains the number of registers used in the buffer.
Valid range is from 2 - 100.
EUCA
Description
The Engineering Unit Conversion and Alarming (EUCA) function provides a single ladder
logic instruction for configuring the scaling of raw analog input values and checking the
values against alarm limits.
Top Node
Contains the alarm status of up to four
analog inputs. Use a 4XXXX reference.
Middle Node
Contains the control table, which has the
raw value, the scaled value, the engineering
unit maximum and minimum, the dead
band, and the alarm limits. Use a 4XXXX
reference.
Bottom Node
Contains a constant from one to four to
select which nibble of the status register to
use.
FN10
Description
The FN10 custom loadable is used to communicate to the MMC188/40.