Download Siemens BH17 7ER Installation guide
Transcript
Mobility and Logistics, Traffic Solutions Sopers Lane, Poole, Dorset, BH17 7ER Designation Description S1 Battery isolation switch. Isolate battery before transportation. Table 15 – PSU Board Switches 4.6.5 Changing Fuses See section 7.3.5 for fuse change procedure. 4.6.6 PSU Board address The PSU board is a GSPI peripheral and as such is addressed in the normal way as an I/O board. The address is fixed at 15 and is not user selectable. Address 15 must not be used by any other GSPI peripheral if a PSU board is present in the system. 4.6.7 Replacing a faulty PSU board The PSU board is not considered to be a field replaceable part as the unit needs to be fully disassembled to replace it. If the PSU board is thought to be faulty, return the complete unit for repair. 4.7 Inbuilt Backup Battery The inbuilt sealed lead acid backup battery should be replaced as routine maintenance typically every 3-5 years under normal circumstances to ensure that the backup time is adequate for instation communications during a power failure. The battery test (see below) can be used to determine exactly when to replace the battery. If the application demands backup at extremes of temperature (outside -20°C to +60°C), then an external battery can be connected to the Power supply board via the rear 10 way connector. If this option is used, note that: 1. The internal battery MUST be disconnected. Unplug and/or remove the internal backup battery as described in section 7.3.4. 2. Any external battery MUST be a lead acid type and 12V. 3. The external lead acid battery is should be connected to the General Functions connector, negative to pin 9, Positive to pin 10 – refer to Table 13. 4. An external battery MUST be fused externally with an in-line fuse holder and 5A quick blow fuse. 5. The internal battery charger will charge an external lead acid battery. 6. There is no limit to the size/capacity of any external battery. The system firmware will automatically shut the system down after 1 minute following a power failure so there is no benefit in increasing external battery capacity above the capacity required for 1 minutes running at the system load and with minimum operating temperature in mind (where battery capacity is reduced). Security classification Unrestricted Page 34 of 84 Version 1 Status Issued Last Editor Carl Rabe Date 11-Dec-2014 Document Name Stratos Outstation General and ICM Handbook Document No. 667/HB/52250/000 Copyright © Siemens plc 2014. All Rights Reserved. Mobility and Logistics is a division of Siemens Plc