Overview of alarms
NCK alarms/ISO alarms
8044
Option for IPO cycle time %1 ms not set
Parameters:
%1 = illegal IPO cycle
Definitions:
The option for activation of an IPO cycle time of %1 ms has not been set.
Option - Permiss. IPO cycle time:
• Option-free >= 8 ms
• 1st step >= 6 ms
• 2nd step >= 4 ms
• 3rd step >= 2 ms
• 4th step < 2 ms
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
• Buy option
• Increase IPO cycle time (e.g. via MD IPO_SYSCLOCK_TIME_RATIO)
Program Continuation:
Switch control OFF - ON.
8045
Option for selected cycle settings not set
Definitions:
The option for the 810D Powerline for activation of the same current/speed/position controller/IPO
cycle time grid as with the 840D is not set. Without the option, only the set values of the 810D Standard
are permitted.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
- Buy option
- Set (current/speed controller) cycle times to 810D default values.
Program Continuation:
Switch control OFF - ON.
8050
Option 'SPL inputs/outputs' not set.
Definitions:
The number of PLC I/Os has not been set in the option date for Solution Line.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Select area SI Basic or SI Comfort in the option date.
Program Continuation:
Switch control OFF - ON.
8051
Option 'Handwheel on PROFIBUS' not set
Definitions:
The option to operate handwheels on PROFIBUS is not set.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Activate option 'Handwheel on PROFIBUS'
Program Continuation:
Switch control OFF - ON.
8080
%1 option(s) is/are activated without setting the license key
Parameters:
%1 = Number of non-licensed options
Definitions:
Options were activated but no license key set to prove that they were purchased.
Reaction:
Alarm display.
Remedy:
Generate license key via Internet and enter.
Take back option.
Program Continuation:
Clear alarm with the Delete key or NC START.