A.2 System Alarms
Number
Effect/cause
Remedy
90024
No operator actions can be logged due to lack of
space on the storage medium for log. The operator
action will therefore not be executed.
Make more space available by inserting an empty storage
medium or swapping out the log files on the server using
"ExportLog".
90025
No user actions can be logged because of error
state of the archive. Therefore the user action will
not be executed.
check whether the storage medium is correctly inserted.
90026
No operator actions can be logged because the log
is closed. The operator action will therefore not be
executed.
Before further operator actions are carried out, the log
must be opened again using the system function
"OpenAllLogs". Change the configuration as required.
90029
Runtime was closed during ongoing operation
(perhaps due to a power failure) or a storage
medium in use is incompatible with Audit Trail. An
Audit Trail is not suitable if it belongs to another
project or has already been archived.
Ensure that you are using the correct storage medium.
90030
Runtime was closed during ongoing operation
(perhaps due to a power failure).
—
90031
Runtime was closed during ongoing operation
(perhaps due to a power failure).
—
90032
Running out of space on the storage medium for
log.
Make more space available by inserting an empty storage
medium or swapping out the log files on the server using
"ExportLog".
90033
No more space on the storage medium for log. As
of now, no more operator actions requiring logging
will be executed.
Make more space available by inserting an empty storage
medium or swapping out the log files on the server using
"ExportLog".
90040
Audit Trail is switched off because of a forced user
action.
Activate the "Audit Trail" again using the system function
"StartLog".
90041
A user action which has to be logged has been
executed without a logged on user.
A user action requiring logging should only be possible
with permission. Change the configuration by setting a
required permission for the input object.
90044
A user action which has to be confirmed was
blocked, because there is another user action
pending.
Repeat the user action if necessary.
110000
The operating mode was changed. "Offline" mode
is now set.
—
110001
The operating mode was changed. "Online" mode
is now set.
—
110002
The operating mode was not changed.
Check the connection to the controllers.
check whether the address area for the area pointer 88
“Coordination" in the controller is available.
110003
The operating mode of the specified controller was
changed by the system function
"SetConnectionMode".
The operating mode is now "offline".
—
110004
The operating mode of the specified controller has
been changed by the system function
"SetConnectionMode".
The operating mode is now "online".
—