Download TP 277, OP 277 (WinCC flexible) - Service, Support

Transcript
Appendix
A.2 System Alarms
Number
Effect/cause
Remedy
110005
An attempt was made to use the system function
SetConnectionMode to switch the specified
controller to "online" mode, although the entire
system is in "offline" mode. This changeover is not
allowed. The controller remains in "offline" mode.
Switch the complete system to "online" mode, then
execute the system function again.
110006
The content of the "project version" area pointer
does not match the user version configured in
WinCC flexible. WinCC flexible Runtime is
therefore closed.
Check:
• the project version entered on the controller
• the project version entered in WinCC flexible
120000
The trend is not displayed because you configured
an incorrect axis to the trend or an incorrect trend.
Change the configuration.
120001
The trend is not displayed because you configured
an incorrect axis to the trend or an incorrect trend.
Change the configuration.
120002
The trend is not displayed because the tag
assigned attempts to access an invalid controller
address.
check whether the data area for the tag exists in the
controller, the configured address is correct and the value
range for the tag is correct.
130000
The action was not executed.
Close all other programs.
Delete files no longer required from the hard disk.
130001
The action was not executed.
Delete files no longer required from the hard disk.
130002
The action was not executed.
Close all other programs.
Delete files no longer required from the hard disk.
130003
No data medium found. The operation is canceled.
Check, for example, if
• the correct data medium is being accessed
• the data medium is inserted
130004
The data medium is write-protected. The operation
is canceled.
check whether access has been made to the correct data
carrier. Remove the write protection.
130005
The file is read only. The operation is canceled.
check whether access has been made to the correct file.
Edit the file attributes if necessary.
130006
Access to file failed. The operation is canceled.
Check, for example, if
• the correct file is being accessed
• the file exists
• another action is preventing simultaneous access to
the file
130007
The network connection is interrupted.
Records cannot be saved or read over the network
connection.
Check the network connection and eliminate the cause of
error.
130008
The storage card is not available.
Insert the storage card.
Records cannot be saved to / read from the storage
card.
130009
The specified folder does not exist on the storage
card.
Any files saved to this directory are not backed up
when you switch off the HMI device.
Insert the storage card.
130010
The maximum nesting depth can be exhausted
when, for example, a value change in a script
results in the call of another script and the second
script in turn has a value change that results in the
call of yet a further script etc.
The configured functionality is not supported.
Check the configuration.
TP 277, OP 277 (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DH01-0AB0
A-11