A.2 System Alarms
Number
Effect/cause
Remedy
200005
No more data is read or written. Possible causes:
• The cable is defective.
• The PLC does not respond, is defective, etc.
• System overload.
Ensure that the cable is plugged in and the controller is
operational.
Restart the system if the system alarm persists.
200100
Coordination is not executed because the address Change the address or set up the address in the
configured in the controller does not exist/is not set. controller.
200101
Coordination is canceled because the write access
to the address configured in the PLC is not
possible.
Change the address or set the address in the controller at
an area which allows write access.
200102
Coordination is not carried out at the moment
because the address format of the area pointer
does not match the internal storage format.
Internal error
200103
Coordination can be executed again because the
last error state is eliminated (return to normal
operation).
—
200104
The coordination may not be executed.
—
200105
No more data is read or written. Possible causes:
• The cable is defective.
• The PLC does not respond, is defective, etc.
• System overload.
Ensure that the cable is plugged in and the controller is
operational.
Restart the system if the system alarm persists.
210000
Jobs are not processed because the address
configured in the controller does not exist/has not
been set up.
Change the address or set up the address in the
controller.
210001
Jobs are not processed because read/write access
to the address configured in the controller is not
possible.
Change the address or set up the address in the
controller in an area which allows read/write access.
210002
Jobs are not executed because the address format
of the area pointer does not match the internal
storage format.
Internal error
210003
The job buffer is processed again because the last
error status has been eliminated (return to normal
operation).
—
210004
It is possible that the job buffer will not be
processed.
—
210005
A control request with an illegal number was
initiated.
Check the controller program.
210006
An error occurred while attempting to execute the
control request. As a result, the control request is
not executed. Observe the next/previous system
alarms.
Check the parameters of the control request. Recompile
the configuration.
220001
The tag is not downloaded because the associated
communication driver / HMI device does not
support the download of Boolean/discrete data
types.
Change the configuration.
220002
The tag is not downloaded because the associated
communication driver / HMI device does not
support write access to the data type BYTE.
Change the configuration.
220003
The communication driver cannot be loaded. The
driver may not be installed.
Install the driver by reinstalling WinCC flexible Runtime.