MP 277 - Service, Support Download

Transcript
Configuring the device
6.10 Change the communication settings
3. If more masters are connected to the bus, deactivate the check box "Panel is the only
master on the bus".
4. Enter the bus address for the HMI device in the "Address" text box.
Note
The bus address in the "Address" text box must be unique throughout the
MPI/PROFIBUS DP network.
5. Select the transmission rate in the "Transmission Rate" text box.
6. Select the highest station address on the bus in the "Highest Station Address" or "Highest
Station" text box.
7. Select the desired profile from the "Profile" selection box.
8. The profile information is displayed when you select "Bus Parameters" button in the
PROFIBUS dialog. The "Profile" dialog is read-only.
Note
The bus parameters must be the same for all stations in the MPI/PROFIBUS DP network.
9. Close the "Profile" dialog.
10. Confirm your entries in the "MPI" or "PROFIBUS" dialog.
The dialog box closes.
The MPI/PROFIBUS DP settings of the HMI device have been changed.
MP 277
108
Operating Instructions, 07/2014, A5E02479740-02