Planning application
3.3 Preparing for Mounting
Dimensions of the mounting cut-out
The following table shows the dimensions of the required mounting cut-out:
Mounting cut-out
MP 277 8" Touch
MP 277 8" Key
MP 277 10" Touch
MP 277 10" Key
Width
226+1
338+1
310+1
mm
434 +1 mm
Height
166+1 mm
206 +1 mm
248+1 mm
291+1 mm
Depth
61 mm
61 mm
61 mm
60 mm
mm
mm
Mounting compatibility
The mounting cut-outs of the Multi Panels are compatible with the mounting cut-outs of the
following SIMATIC HMI devices:
Multi Panel mounting cut-out
Compatible to the mounting cut-outs of the HMI device
MP 277 10" Touch
Thin Client 10" Touch
MP 270B 10" Touch
MP 277 10" Key
KTP1000 Basic
MP 277 INOX 10" Touch
TP 270 10"
MP 377 12" Touch
MP 270B 10" Key
OP 270 10"
Maintaining clearances
The HMI device must be installed with the following clearances:
● Always allow 50 mm above and below the mounting cutout respectively for ventilation
● Right and left of the mounting cutout respectively for attaching the mounting clips:
– When using a clamping frame: 25 mm each
– Without clamping frame, with spring mounting clips: 25 mm each
– Without clamping frame, with aluminum mounting clips: 15 mm each
● At least 10 mm behind the rear panel of the HMI device
Note
Ensure that the maximum ambient temperature is not exceeded when mounting the
device in a cabinet and especially in a closed enclosure.