MP 277 - Service, Support Download

Transcript
Overview
1.9 Functional scope with WinCC and WinCC flexible
Recipes
Object
Specification
Recipes
Number
WinCC
300
Data records per recipe
500
Entries per recipe
1000
Recipe memory
64 KB
Storage location
1
WinCC flexible
•
Memory card 1
•
USB memory stick 1
•
Network drive
The number of recipe data records may be restricted by the capacity of the storage medium.
Logs
Note
The HMI devices are suitable for the logging of relatively small volumes of data.
Manage the data in several adjacent archives in a segmented circular log. The use of a large
circular log has a negative effect on performance.
Object
Specification
WinCC
Logs
Number of logs
20
Number of partial logs in a segmented circular log
400
Entries per log
10000
Filing format
Storage location
1
WinCC flexible
CSV with ANSI character set
•
Memory card 1
•
USB memory stick 1
•
Network drive
The number of entries in the log may be restricted by the capacity of the storage medium.
Safety
Object
Specification
WinCC
WinCC flexible
Safety
Number of user groups
50
Number of users
50
Number of authorizations
32
MP 277
20
Operating Instructions, 07/2014, A5E02479740-02